VFD v4 calculator — local preview

Eco Wave Green · Learning examples

Explore the relationships

VFD calculator: explore energy use

Explore how speed, motor size and operating hours affect illustrative electricity use. Compare synthetic results and review the assumptions and evidence a real assessment would need.

Synthetic illustration of a dark green electric motor coupled to a centrifugal pump with silver pipework and an enclosed coupling.

Smarter systems for a cleaner tomorrow

  • Lower energy use
  • Higher operational efficiency
  • A more sustainable future
  • Explore

    See how speed and operating hours affect illustrative electricity use.

  • Compare

    Compare synthetic results against a stated reference.

  • Understand

    Review assumptions, limitations and the evidence a real comparison needs.

Eco Wave Green · development prototype · synthetic learning only

See what variable speed changes

A fictional centrifugal fan helps explain the relationship between speed, airflow and mechanical shaft power. These are educational comparisons, not equipment instructions.

Interactive readings are unavailable until this prototype's script completes setup. The explanation and calculation limits remain useful; no annual electricity result has been calculated.

From electricity to airflow

1 · Electricity supply

Electrical input

2 · VFD controller

Controls a compatible motor

3 · Motor

Delivers mechanical shaft power

4 · Centrifugal fan → airflow

Provides a changing service

The VFD controls the motor supply; the motor and fan are directly coupled here. Conceptual illustration only: any motion represents neither measured airflow nor motor/fan RPM.

View calculation details

With speed ratio r, idealised airflow is r, pressure is r² and mechanical shaft power is r³, each relative to its own reference. Geometry and fluid density stay unchanged; corresponding points, constant fan efficiency and a friction-only system are assumed. Real operating points and fixed pressure can change the relationship.

At 80% speed the example gives 80% airflow, 64% pressure and 51.2% shaft power. No electrical saving follows from those percentages alone.

Reference shaft kW = motor rating × load fraction. Selected shaft kW = reference shaft kW × speed ratio³. At positive speed electrical input divides shaft power by the stated motor efficiency, and by drive efficiency on the selected side. At 0% selected running input is inactive (zero); selected running efficiencies are ignored and selected annual electricity = 8,760 × complete selected standby kW. Reference calculation retains its entered running/standby durations. Annual energy for a running arrangement = its running hours × electrical kW + its standby hours × complete standby kW. Difference = reference minus selected; a negative difference means higher selected use.

When might a VFD not reduce electricity use?

At unchanged shaft duty, a drive adds conversion losses. With the adopted example loaded, move the slider to 100%: the fan provides its reference shaft duty, while selected electrical use is higher because of the assumed drive loss. Different motor efficiencies and standby inputs also affect the result. Equal, higher and unavailable outcomes remain valid.

This example does not establish eligibility for an installation. Fixed pressure, required service and real efficiency may differ. Existing-VFD optimisation, non-centrifugal or uncertain equipment, hazardous areas, fire/smoke/emergency/life-support and health, safety or process-critical applications are outside scope. Preserve ventilation, process and environmental safeguards. Obtain competent assessment before any equipment change; this prototype gives no sizing, selection, compatibility, design, installation or operating approval.

The specialist scenario workspace remains in the original calculator. This parallel local prototype supplies no guarantee of savings, funding, compliance or other outcomes.

Local learning summary

No interactive calculation is available. Annual electricity, cost and emissions are unavailable. Review the stated assumptions and scope before using any example.

Build a stronger comparison

What would support a site comparison?

A motor label and chosen frequency are not enough. A supported comparison needs matched service, representative operating hours and evidence for both electrical-power profiles.

  1. Equipment and control

    Identify the centrifugal pump or fan and how it is regulated.

    Use records or operator knowledge, with competent confirmation when uncertain.

  2. Required service

    Establish required flow, pressure or ventilation, timing and protected needs through records and a competent system/process assessment.

  3. Electrical power

    Support existing and proposed electrical input at each duty on the same boundary.

    A motor rating is not an operating-power measurement.

  4. Running and standby profile

    Establish representative duties, seasons, hours and non-running consumption.

    Check that the profile represents the intended period.

  5. Suitability and responsibility

    Appropriately authorised, competent people establish equipment compatibility, permitted operation and electrical/process responsibilities within their respective scopes.

“Not known” is a normal evidence gap. Gather existing records; do not guess or open equipment to fill it. Establishing missing technical evidence is a separate assessment.

No drive, operating speed or supplier is selected. A competent pump/fan and process assessment is separate. Electrical work requires appropriate authorisation.

Sources and limits

M0 powers are EWG fictional teaching fixtures. M1 uses entered synthetic powers and evidence assertions, not independently verified site measurements. These sources support the explanations and qualifications; their organisations have not reviewed or endorsed this example.

Source records reviewed in the research on 18 September 2026. Links have not been freshly checked for this build. Historical efficiencies are not current equipment defaults; high-level electrical referral is not a complete legal interpretation.